The model WB-800 operates on 12 or 24 Volt AC/DC and has a
form C relay output that can be connected to alarm panels, bells, dialers,
etc. Unit also includes internal alarm buzzer with silence switch and
eight LEDs on console to identify the sensor in alarm. As many as eight
supervised sensor probes can be run up to 500 feet away (or 16
non-supervised sensors). Each sensor probe has two contacts. When a film
of water forms a bridge between these contacts, the unit senses this and
triggers the alarm output. The sensor will not alarm due to condensation
or high humidity. Four standard surface sensors are included with the
unit.
|
SPECIFICATION |
VALUE FOR WB-800 |
|
Console Size |
6.55" x 4.70" x 1" (16.6 cm x 11.9 cm x 2.5 cm) |
|
Probe Size (standard P/N #1040) |
2" x 3" x 0.88" (5.1 cm x 7.6 cm x 2.2 cm) |
|
Probe Size (under carpet P/N #1041) |
2" x 3" x 0.18" (5.1 cm x 7.6 cm x 0.5 cm) |
|
Power Requirements |
12V or 24V AC or DC |
|
Current Draw (resting state) |
75mA @ 12V or 24VDC, or 200mA @ 12V or 24VAC |
|
Current Draw (alarm condition) |
125mA @ 12V or 24VDC, or 330mA @ 12V or 24VAC |
|
Sensitivity |
Will not alarm due to high humidity or condensation |
|
Operating Temperature |
Control and Probe 32º to +140º F (0º to +60º C) |
|
Outputs |
Form C (SPDT) 1 Amp @ 24Vac, 1 Amp @ 30 VDC (not for direct high voltage switching) Audible alarm with silence feature |
|
Recommended Dist. Between Probes & Console |
500ft (152.4 m) maximum |
|
Recommended Max. Probes Per Console |
8 supervised or 16 non-supervised |