RZA-4XF Remote Annunciator
The RZA-4XF Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the same functions as the 4XZMF Zone Relay Module. For example, with DIP 1=ON and DIP 2=OFF:
- One Zone in Alarm (red)
- Two Zones in Alarm (red)
- Releasing Circuit 1 (red)
- Releasing Circuit 2 (red)
- System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate.
|