BEAM1224 Reflected Type Beam Smoke Detector
The BEAM1224 is a 4-wire, single-ended, reflected type beam smoke detector that includes an 8" reflector.
System Sensor Model BEAM1224 is a 4-wire conventional projected beam smoke detector. It is uniquely suited for protecting open areas with high ceilings where other methods of smoke detection are difficult to install and maintain. It is to be used with UL Listed compatible control panels only. Installation of the single-ended reflective design is much easier than the dual-ended projected beam detectors. Alignment is quickly accomplished via an optical sight and a 2-digit signal strength meter incorporated into the product. Listed for operation from –22°F to 131°F, BEAM1224 can be used in open area applications to provide early warning in environments where temperature extremes exceed the capability of other types of smoke detection.
BEAM1224 consists of a transmitter/receiver unit and a reflector. When smoke enters the area between the unit and the reflector it causes a reduction in the signal and, when the smoke level reaches the predetermined threshold, an alarm is activated.
BEAM1224 has four standard sensitivity selections along with two Acclimate settings. When either of the two Acclimate settings are selected the detector will automatically adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the specific environment.
BEAM1224S is equipped with an integral sensitivity test feature that consists of a test filter attached to a servo motor inside the detector optics. Using the remote test station RTS451, the motor is activated and moves the filter in the pathway of the light beam, thereby testing detector sensitivity. This integral sensitivity test feature allows the user to quickly and easily meet the annual maintenance and test requirements of NFPA 72.
Specifications
- Detection: Infrared Beam
- Wiring: 4-wire
- Operating Voltage: 10.2 to 32 VDC
- Alarm Current: 38.5mA max. avg.
- Standby Current: 17mA max. @ 24 VDC
- Trouble Current: 8.5mA max. @ 24 VDC
- Temperature Range: -22°F to 131°F (-30°C to 55°C)
- Humidity Range: 10% to 93% RH noncondensing
- Range: 16 ft. to 328 ft. (5m to 100m)
- Sensitivity: Level 1 - 25%; Level 2 - 30%; Level 3 - 40%; Level 4 - 50%; Acclimate Level 1 - 30-50%; Acclimate Level 2 - 40-50%
- Dimensions: Detector: 10" H x 7.5" W x 3.3" D (254mm x 191mm x 84mm); Reflector, 16-230ft.: 7.9" H x 9.1" W (200mm x 230mm)
Additional Information
|