The feature-rich VISTA-40 Control Panel is a cost-effective solution for almost any application. Features include advanced partitioning, end-user simplicity and compatibility with the best wireless technology today. A powerful control, the VISTA-40 can support residential installations and operate lights and appliances – providing you with greater installation flexibility while offering your customers the ultimate in convenience.

Honeywell 4208U V-Plex Universal Eight Zone Remote Point Module

Honeywell 4208U V-Plex Universal Eight Zone Remote Point Module

Honeywell 4208U V-Plex Universal Eight Zone Remote Point Module

V-Plex™ Universal Eight Zone Remote Point Module

The ADEMCO 4208U Remote Point Module (RPM) is an eight-zone expander that allows the use of available expansion zones on ADEMCO controls that support V-Plex polling loop devices.

Features

  • Can be optionally powered from an external DC power supply to reduce the amount of current draw from the polling loop
  • Uniquely identifies eight EOLR supervised zones (all zones use 10K resistors, supplied)
  • DIP Switches can be used to set zone numbers or serial numbers
  • When used in the serial number mode, each serial number in the selected group can be assigned to any zone number
  • Loops A & B can be programmed for fast (10msec) response
  • Provides cover tamper protection, which may be enabled or disabled via on-board DIP Switches
Specifications
  • Physical:
    Width: 6-7/16" (163mm)
    Height: 4-1/4" (108mm)
    Depth: 1-1/4" (32mm)
  • Electrical:
    Polling Loop input: 7.3 - 14VDC range
    Current draw: 28.6mA max. External power and polling loop
    See chart below.
  • External Power Input (optional): 12VDC @ 28mA (from control panel’s auxiliary power)
  • Sensor Loop Response :
    Slow: 400 msec (all loops)
    Fast: 10msec (option for loops A and B)
  • Sensor Loop Current :
    Polling loop input = 11VDC, no external power input):
    0.52mA (normal)
    1.3mA (shorted)
  • Sensor Loop Max. Current : Up to 300 ohms of wire resistance + 10K EOLR
  • Agency Listings :
    UL 985 Household Fire
    UL 1023 Household Burglary
    UL 609 Commercial Burglary
    UL 864 Commercial Fire
    CSFM
    FM
    CUL
    CE (requires #N6361)

Power Input Source
(Input Voltage: 11-14VDC)

Current Draw  (all zones shorted)

From Polling Loop

From External Power

Polling Loop Only

33.6mA 

N/A

Polling Loop and
External Power Input

0.6mA

33mA

For UL Listed Commercial Fire Usage:
Use N.O. contacts. Style B supervise these loops using Model #EOL 100 fire listed 10K EOLRs (purchased separately).
For UL Listed Commercial Burglary Usage:
Use N.O. or N.C. contacts. Supervise using EOLRs supplied.
Ordering Information
Part No. Description
4208U 8 Zone Expander

Product #4208U
Price: US $90.99